第一篇:板式換熱器容積式換熱器技術要求
板式換熱器容積式換熱器技術要求
一、技術標準
投標產品應符合(但不僅限于)如下標準及現行國家、地方、廠家、各政府部門的各種規范、法規、規定中的相關要求:
1.GB16409-1996 板式換熱器
2.GB150-98 鋼制壓力容器
3.GB151-89 鋼制管殼式換熱器
4.壓力容器安全檢查規程(國家勞動總局頒發)
5.GB699-88 優質碳素結構鋼技術條件
6.GB6654-96 壓力容器用碳素鋼及不同低合金鋼熱軋厚鋼板
7.JB4701~4702-92 壓力容器法蘭
二、1.2.3.4.板式換熱器技術要求 采暖熱負荷:高區供熱負荷為5970KW,低區供熱負荷為7613KW; 一次水供回水溫度為125℃/65℃,二次水供回水溫度85℃/60℃; 工作壓力:高區1.6 MPa,低區1.0MPa; 材質要求:傳熱板片采用不銹鋼SUS304,密封膠墊采用三元乙丙橡膠或等效的其他材料。
三、立式即熱式容積式換熱器技術要求
1.生活熱水熱負荷:高區生活熱水負荷為2200KW,低區生活熱水負荷為4000KW;
2.一次水供回水溫度:冬季125℃/65℃,夏季70℃/40℃;高低區生活熱水供回水溫度55℃/12℃;
3.工作壓力:高區1.6 MPa,低區1.0MPa;
4.材質要求:殼體采用16MnR,換熱管采用不銹鋼波節管或性能等效的其他材料。
四、1.2.3.4.設計選型參數(供參考)高區采暖板式換熱器,2臺,F=45.65m2,Q=4179KW; 低區采暖板式換熱器,2臺,F=57.75m2,Q=5329KW; 高區立式即熱式容積式換熱器,2臺,F=46m2,V=5m3; 低區立式即熱式容積式換熱器,3臺,F=46m2,V=5m3;
五、其他要求
1.換熱器的設計和制造采用的零件、標準件等均應按照國家標準和相關部標驗收;
2.供方應向需方提供有關換熱器試驗報告和完整的質量保證書;
3.需提供選型報告,并提供換熱器各組件的材質;
4.供方提供的產品需確保能滿足安裝使用要求并能通過熱力集團有關部門的驗收。
第二篇:管殼式換熱器技術要求
管殼式換熱器技術要求
管殼式換熱器技術要求
編
制:鄢勝軍
2015年 6 月 9 日 汽機車間:
****年**月**日 技 術 部:
****年**月**日 裝 備 部:
****年**月**日 生 產 部:
****年**月**日 安 環 部:
****年**月**日 總
師:
****年**月**日 主管廠長:
****年**月**日
汽機車間
技術類
管殼式換熱器技術要求
管殼式換熱器技術要求
一、換熱器現狀
襄陽熱電廠目前使用的兩臺75m臥式管殼式換熱器用于移動供熱加熱自來水,目前主要存在如下問題,需對兩臺換熱器進行大修:
1、換熱器的冬季供水量偏小:2014~2015年冬季移動供熱的熱電廠產能與客戶需求的矛盾突出,每小時供水量約為40t/臺,最大日供水量900t左右,難以滿足市場要求。
2、換熱器無安全閥、壓力表,不符合TSG 0004-2009《固定式壓力容器安全技術監察規程》要求。
二、換熱器大修工作范圍
1、型式:臥式管殼式換熱器
2、數量:兩臺
注:①包含配套附件及壓力表、安全閥、水位計等 ②供貨方應承擔設備的往返運輸費用
2三、換熱器大修后應達到的設備參數
1、換熱方式:汽-水表面式換熱器
2、換熱面積:75 m/臺
3、加熱蒸汽參數:壓力0.08~0.15MPa,溫度150~230℃
汽機車間
技術類
2管殼式換熱器技術要求
4、被加熱介質:自來水,壓力0.2~0.4MPa
5、換熱器額定供水能力為每臺50t/h,水溫升為80℃
四、換熱器技術要求
1、換熱器在設計、原材料采購、制造、檢驗及運輸過程
中,嚴格按照GB/T 151-2014《熱交換器》標準執行。
2、換熱器的型式為臥式,結構為單殼程雙管程方式,且 管束與殼體應為可拆卸式。
3、換熱器中管程走水,殼程走汽。
4、換熱器中水的流程為下進上出,汽的流程為上進下出。
5、換熱器的進汽及出水法蘭接口應盡可能根據現場管道
情況改造。
6、換熱器材料的選擇原則:鋼材按GB150-2011《鋼制壓力容器》標準選用。殼體為壓力容器用鋼Q345R,內部管程為304材料,管板為Q345R。
7、換熱管采用直管型式。
8、換熱器汽側應設置水位計接口,水位計為磁翻柱式。
9、換熱管的漲口處理方式應在產品說明書中明確。
10、換熱管端蓋連接采用金屬墊,并提供備用金屬墊一套。
11、換熱器的裝箱資料中應有產品說明書、出廠合格證、質量保證書、壓力容器檢驗合格證、打壓試驗記錄、材質報告等技術文件。
汽機車間
技術類
管殼式換熱器技術要求
五、安全保障
1、換熱器汽側和水側應提供配套安全閥及壓力表。
2、換熱器制造應符合GB/T 151-2014《熱交換器》及GB150-2011《鋼制壓力容器》標準。
六、工期
換熱器應在自合同簽訂之日起40日內到貨。
七、質保期
設備投運驗收合格后,質保期壹年。
八、投標要求
投標方應根據上述技術要求及相關國家規范進行設備 的設計、原材料采購、制造、檢驗、運輸。
投標方應在投標文件中明確以下幾項內容:
1、應明確表明是否響應招標技術要求相關條款;
2、上述技術要求是最低技術要求,投標方的承諾不得低于上述技術要求及相關國家規范;
3、投標方應提供換熱器的設計圖紙;
4、投標方應提供工程量清單。
汽機車間
技術類
第三篇:換熱器設計任務書格式要求
化工原理課程設計任務書
設計工作的重要性:2個學分 工作具體要求:
1所有計算過程要求留草稿(軟皮本或信箋紙均可),要檢查。2本學期末計算到“傳熱面積估算”,如有問題及時反映,好調整參數。3下學期開課第一周交“手寫版初稿”,內容“3-致謝”。經檢查計算無誤,進行電子錄入。4下學期第6周上交“電子版初稿”完整版。
5第7-8周進行格式修改,第8周周末前交“電子版終稿”。6第17周前交圖紙。
電子版格式要求:
1封面:封面包括如下內容
(1)題目
(2)學生:姓名、學號、系別、年級、學科、專業;(3)指導教師:(姓名、職稱);
(4)完成日期:××××年××月××日。
2摘要:摘要要有高度的概括,語言精煉、明確。同時有中、英文摘要及關鍵詞,中英文摘要字數在300字左右。關鍵詞挑選3~5個最能表達主要內容的詞或術語。排序如下:
(1)中文摘要、關鍵詞;(2)英文題目、摘要、關鍵詞。
3目錄:目錄作為論文(設計)提綱,是論文(設計)各組成部分的小標題,文字應簡明扼要。目錄按論文(設計)順序用三級標題編寫(如:“1?、1.1?、1.1.1?”或“第一章?、第一節?、1.?”或“
一、? 1.?(1)?”),并標明頁碼。目錄中的標題、頁碼應與正文中的標題、頁碼一致。4參考文獻:
5致謝:致謝通常以簡短的文字,對工作過程中曾給自己以直接幫助的人員,表示自己的謝意。6打印排版
統一用A4紙單面打印裝訂,上邊距為3.0cm,下邊距為2.5cm,左邊距為2.5cm,右邊距為2.5cm。①設計題目為三號黑體字,可以分為1或2行居中打印。設計題目下空一行打印摘要,[摘要]二字(四號黑體,居中),[摘要]二字下空一格打印內容(小四號宋體)。摘要內容下空一行打印[關鍵詞]三字(小四號黑體),其后為關鍵詞(小四號宋體)每兩個關鍵詞之間用分號隔開。英文摘要全部用Times New Roman字體,題目四號加粗,摘要內容和關鍵詞均用小四號,Abstract和Key words加粗。中文題目、中文摘要、關鍵詞合打一頁;英文題目、英文摘要和關鍵詞另打一頁(若中英文摘要較短時,也可合打一頁上)。
②目錄:[目錄]二字(四號黑體,居中),下空一行為章、節、小節(或
一、1.(1)? ?,理工科可用1?、1.1?、1.1.1?編號)及其開始頁碼,采用小四號宋體。頁碼放在行末。目錄內容和頁碼之間用虛線連接。目錄不與摘要在同一頁,要單獨成頁。
③正文(引言、研究方法、討論與分析、結論):正文用小四號宋體字打印(若有標題,章標題以小三
號黑體,居中打印;節標題以四號黑體字左起打印;小節標題以小四號黑體字左起打印)。正文從第1頁開始編頁碼。
④文中圖、表:標目采用國家標準的物理量(英文斜體T、P、V)和單位符號(英文正體)的比表示,如kg/m3。表格采用“三橫線表”,表的內容切忌與圖和文字的內容重復。全部正文中出現的表格按表1,表2,表3等依次編號。【表1】字后空兩格。表頭及表中文字采用小五號字體。表頭加粗。
表1 冷熱流體物性數據表
比熱/ 物料
密度/kg/m
kJ/(kg·K)煤油 河水
810 994.8
2.3 4.2
0.91 0.76
3導熱系數
粘度/10Pa·s
/W/(m·K)
0.13 0.62
⑤公式:公式書寫應在文中另起一行,居中書寫。公式的編號加圓括號,放在公式右邊行末,公式和編號之間不加虛線。公式后應注明編號,該編號按章順序編排。具體要按下例進行排版:
qm,c?QcCp,c(t2?t1)
(5—1)
式中:qm,c——低溫流量的質量流量,kg/s;
QC——冷流體所吸收的熱量,W;
Cp,c——水的定壓比熱容,kJ/(kg·K);
。t1、t2——分別為低溫流體的進出口溫度,℃代入數據得:qm,c?8018954.17?10(40?26)3?13.7kg/s
⑥致謝:[致謝]二字用小四號仿宋體加黑,內容為小四號仿宋體。⑦特別注意:完整的一段文字,首行縮進2字符。全篇采用1.5倍行距。⑧其他要求
全文內的各章、各節內的標題及段落格式(含頂格或縮進)要一致; 設計說明書裝訂順序:
封面→中文摘要→英文摘要→目錄→正文→參考文獻→致謝。
9.5萬噸/年煤油冷卻器設計
摘 要
本設計論文介紹了固定管板式換熱器的整體結構設計及計算。固定管板式換熱器制造方便、單位體積內換熱面積大、造價低廉,但是兩端都固定在固定管板上,冷熱流體溫差較大時產生的熱應力較大,可能損壞換熱器。因此,固定管板式換熱器只適用于冷熱流體溫差低于70℃(高于50℃時加溫度補償)的換熱任務。此類換熱器殼程流體應選擇不易結垢的流體,以解決不易清洗的弊端。固定管板式換熱器主要結構包括封頭、管箱、換熱管、折流擋板、支座及其它附件等。
本設計任務溫度和壓強要求都不高,由換熱器的系列標準選取B E M 400-0.6-46.2-625-1Ⅱ固定管板式換熱器。經傳熱面積、壁溫、壓降的核算證明此換熱器每年可以完成9.5萬噸/年的煤油冷卻任務。
關鍵詞:固定管板式換熱器;設計計算;煤油冷卻器
9.5 Million tons/year kerosene Cooler Design
Abstract: This paper introduces the design of fixed tube heat exchanger overall structure design and calculation.Fixed tube heat exchanger easy fabrication, unit volume heat-exchange area big, low cost, but both fixed in fixed tube sheet heat fluid, produced when large temperature difference is larger, the thermal stress may damage the heat exchanger.Therefore, fixed tube heat exchanger only applies to the cold heat fluid under 70℃ temperature(more than 50℃ temperature compensation)added when the heat transfer task.Such heat exchanger should choose not easy process fluid shell scaling fluid, and to solve the disadvantages of not easy clean.Fixed tube heat exchanger main structure include sealing head, tube box, heat exchange tube, baffle, bearings and other accessories etc.This design task temperature and pressure by demands are not high, the series standard heat exchanger selecting B E M 400-0.6-46.2-625-1Ⅱ fixed tube heat exchanger.By heat transfer area, wall temperature, pressure drop of accounting proof this heat exchanger can accomplish the cooling task kerosene of 9.5 million tons/year.Key words: Tube heat exchanger;Design calculation;Kerosene cooler
目 錄
0 引言 ······································································································································ 1 0.1 換熱器的應用 ··················································································································· 1 0.2 換熱器的分類 ··················································································································· 1 0.2.1 直接接觸式換熱器 ········································································································ 1 0.2.2 蓄熱式換熱器 ················································································································ 1 0.2.3 間壁式換熱器 ················································································································ 1 0.2.4 中間載熱體式換熱器 ···································································································· 2 0.3 常見及常用的換熱器 ······································································································· 2 0.4 進行換熱器設計的重要意義 ··························································································· 2 1 設計任務 ······························································································································ 2 2 設計方案的確定 ·················································································································· 2 2.1 換熱器類型的選擇 ··········································································································· 3 2.2 管程、殼程物料的安排 ··································································································· 4 3 物性數據的確定 ·················································································································· 4 3.1 定性溫度的確定 ··············································································································· 4 3.2 冷、熱流體有關物性數據 ······························································································· 5
第四篇:技能培訓:噴淋式換熱器
一、噴淋式換熱器的結構型式
噴淋式換熱器是用冷卻水直接在管外噴淋,使管內熱流體冷凝或冷卻,所以一般稱為噴淋式冷卻器,其構造如下圖所示。
噴淋式換熱器
冷卻器的冷卻管之間,是借U形肘管順次聯接在一起,使呈上下排列,而管子的排數可多到10-20排。管子最上面設有水噴淋裝置,如噴頭或水槽等。或用與排管長度相當的鋼管,沿管開有一定數量的小孔作噴淋裝置,噴口向下,噴出之冷卻水靠自由落體的作用,使冷卻水淋灑于排管上。
二、噴淋式換熱器的優缺點
1.噴淋式換熱器的優點
(1)由于冷卻水直接噴淋在排管外壁面上,所以會有一部分水吸收管內熱流體的熱量而蒸發汽化。另外,噴淋式換熱器一般是安裝在室外空氣流通的空間里,空氣也吸收一部分熱量。由于冷卻水和空氣的共同冷卻,所以傳熱效果好,用水量少,在相同的情況下,消耗水量比沉浸式換熱器幾乎要少一半。
(2)對于一定的傳熱面,若安裝高度不受限制,可以把管排做的很窄,使空間占用面積減小。
(3)如果使排管外壁保持清潔,可獲得更好的冷卻效果。對于用冷水冷卻液體時,傳熱系數可達250-800Kca/m2·h·℃,一般情況下,傳熱系數也在200Kca/m2·h·℃左右。對于用冷水冷卻冷凝蒸汽時,傳熱系數可達300-1000Kca/m2·h·℃。
(4)結構簡單、易于制造和清除結垢、成本低、檢修方便。
(5)適于高壓流體的冷卻或冷凝。
2.噴淋式換熱器的缺點
(1)體積較大,占地面積較多,其緊湊性和沉浸式換熱器相近,單位體積的傳熱面積約為16㎡,相當于列管式換熱器的1/6-1/11。
(2)材料耗量大,每單位傳熱面積的材料用量約為列管式換熱器的兩倍,但比沉浸式換熱器和套管式換熱器耗量少。
(3)噴淋式換熱器雖然耗水量少,但對于水源不足或突然停水時,對易產生意外事故的石油產品或有機氣體的冷卻不宜采用。生產中為了克服此種缺點設有涼水塔。使用過的冷卻水,經涼水塔冷卻后再用,從而確保冷卻水的充足供應。
(4)一般情況下,噴淋式換熱器都是露天安裝,冷卻管受風吹日曬,以及與空氣中其他氣體易于發生化學腐蝕,容易造成管外壁的結垢,降低了傳熱效果。
此種換熱器多用作氣體的冷卻,如合成氨生產中由合成塔出來的合成氣和各種氯化產品的氯化尾氣的冷卻,也廣泛用于酸性液體工業中的濃酸的冷卻。
在化學工業中,根據工藝要求及條件不同,除噴淋式換熱器外,其他構造的換熱器也有極其廣泛的應用場景,后續分次介紹。
第五篇:容積式壓縮機
channel valve槽狀閥 dish valve碟狀閥 multistoried valve多層閥 ring valve環狀閥 disk valve網狀閥 leaf valve條狀閥 mushroom valve菌狀閥 combined valve組合閥 direct-flow valve直流閥 reed valve舌簧閥 flap valve舌簧閥 cushion valve氣墊閥
valve stop/valve guard升程限制器
cushion plate緩沖片 damper plate緩沖片 guide plate導片 valve spring氣閥彈簧 oil wiper packing刮油器 packing case填料盒 stuffing填函 pre-stuffing前置填函
mounting pad安裝墊 packing ring密封環 oil wiper ring刮油環 equalizing ring均壓圈 rectangle packing平面調料 tapered packing梯形填料 packing gland填料壓蓋 diaphragm膜片 base plate基座
· 壓縮
機positive displacement compressor
往復式壓縮機(活塞式壓縮機)reciprocating compressor回轉式壓縮
機rotary compressor滑片式壓縮
機sliding vane compressor單滑片回轉式壓縮
機single vane rotary compressor
rolling rotor compressor三角轉子式壓縮
機triangle rotor compressor多滑片回轉式壓縮機
multi-vane rotary compressor滑片 blade旋轉活塞式壓縮機 rolling piston compressor渦旋式壓縮機 scroll compressor渦旋盤scroll固定渦旋
盤stationary scroll, fixed scroll 驅動渦旋盤
driven scroll, orbiting scroll斜盤式壓縮機(搖盤式壓縮
機)swash plate compressor斜盤swash plate搖盤 wobble plate螺桿式壓縮
機screw compressor
single screw compressor陰轉子 female rotor陽轉子 male rotor主轉子 main rotor閘轉子 gate rotor無油壓縮
機oil free compressor膜式壓縮機
diaphragm compressor活塞式壓縮機
reciprocating compressor單作用壓縮
機single acting compressor 雙作用壓縮
機double acting compressor 雙效壓縮機
dual effect compressor雙缸壓縮機
twin cylinder compressor閉式曲軸箱壓縮機
closed crankcase compressor
open crankcase compressor順流式壓縮
機uniflow compressor逆流式壓縮機
return flow compressor干活塞式壓縮機 dry piston compressor雙級壓縮
機compound compressor多級壓縮機
multistage compressor差動活塞式壓縮機
stepped piston compound compressor, differential piston compressor串軸式壓縮機
tandem compressor, dual compressor
截止閥 line valve, stop valve排氣截止
閥discharge line valve
部分負荷旁通口 partial duty port
能量調節器 energy regulator容量控制滑閥
capacity control slide valve容量控制器capacity control消聲器 muffler聯軸節coupling曲軸箱crankcase曲軸箱加熱
器crankcase heater軸封
crankcase seal, shaft seal填料盒stuffing box軸封填料shaft packing機械密封mechanical seal波紋管密封 bellows seal轉動密封 rotary seal迷宮密封 labyrinth seal軸承 bearing
滑動軸承sleeve bearing
偏心環 eccentric strap滾珠軸承ball bearing滾柱軸承roller bearing滾針軸承 needle bearing止推軸承thrust bearing外軸承 pedestal bearing臼形軸承 footstep bearing軸承箱 bearing housing止推盤thrust collar偏心銷eccentric pin曲軸平衡塊
crankshaft counterweight, crankshaft balance weight曲柄軸 crankshaft偏心軸
eccentric type crankshaft曲拐軸
crank throw type crankshaft連桿 connecting rod連桿大頭crank pin end連桿小頭 piston pin end曲軸 crankshaft
主軸頸 main journal曲柄crank arm, crank shaft曲柄銷crank pin曲拐crank throw曲拐機構crank-toggle閥盤valve disc閥桿valve stem閥座valve seat閥板 valve plate閥蓋valve cage閥罩valve cover
閥升程限制器valve lift guard 閥升程valve lift閥孔valve port吸氣口suction inlet
壓縮機氣閥compressor valve 吸氣閥suction valve排氣閥delivery valve圓盤閥 disc valve環片閥ring plate valve簧片閥reed valve舌狀閥cantilever valve
條狀閥beam valve提升閥poppet valve菌狀閥 mushroom valve杯狀閥 tulip valve缸徑 cylinder bore
余隙容積 clearance volume附加余隙(補充余隙)clearance pocket活塞排
量 swept volume, piston displacement理論排
量 theoretical displacement實際排量 actual displacement實際輸氣
量 actual displacement, actual output of gas氣缸工作容
積 working volume of the cylinder活塞行程容
積 piston displacement
氣缸 cylinder氣缸體 cylinder block氣缸壁 cylinder wall水冷套 water cooled jacket氣缸蓋(氣缸頭)cylinder head安全蓋(假蓋)safety head假蓋 false head活塞環 piston ring氣環 sealing ring刮油環 scraper ring油環 scrape ring活塞銷 piston pin活塞 piston
活塞行程 piston stroke吸氣行程 suction stroke膨脹行程 expansion stroke壓縮行程 compression stroke排氣行程 discharge stroke升壓壓縮
機 booster compressor立式壓縮
機 vertical compressor
臥式壓縮
機 horizontal compressor角度式壓縮
機 angular type compressor對稱平衡型壓縮
機 symmetrically balanced type compressor
移動式防爆螺桿式空氣壓縮機 Mobile explosion-proof screw rod type air compressor