第一篇:35kV變電站設(shè)計(jì)方案探討
35kV變電站設(shè)計(jì)方案探討
摘要:本文結(jié)合我地區(qū)35kV變電站的運(yùn)行管理和勘測(cè)設(shè)計(jì),就優(yōu)化35kV變電站設(shè)計(jì)方案問(wèn)題做些探討,合理選擇設(shè)計(jì)方案應(yīng)考慮的問(wèn)題。
關(guān)鍵詞:35kV變電站設(shè)計(jì)、設(shè)計(jì)方案、探討
1.前言
由于農(nóng)村用電負(fù)荷小,面積廣。根據(jù)有關(guān)資料推薦,當(dāng)負(fù)荷密度在10―20kw/km2范圍時(shí),35kV/10kV供電方式的經(jīng)濟(jì)供電半徑為l0―15km,相配套的35kV線路輸送容量為2000―10000kw,輸送距離為20―50km,10kV線路輸送容量20―2000kw。輸送距離為6―20km。因此,35kV變電站適合于農(nóng)村電力網(wǎng)建設(shè),盡管現(xiàn)在在用電量大的城市和經(jīng)濟(jì)發(fā)達(dá)的沿海城市已不再新建35kV變電站,甚至舊的35kV變電站也升壓改造成110kV變電站或10kV開關(guān)站,然而,35kV/10kV供電方式在廣大的農(nóng)村地區(qū)仍將長(zhǎng)期存在,35kV變電站將長(zhǎng)期使用。
一般在農(nóng)網(wǎng)35kV變電站的設(shè)計(jì)時(shí)不僅應(yīng)符合國(guó)家現(xiàn)行的有關(guān)標(biāo)準(zhǔn)和規(guī)范的規(guī)定,還必須對(duì)設(shè)計(jì)方案進(jìn)行技術(shù)經(jīng)濟(jì)比較,加以優(yōu)化。這對(duì)降低工程造價(jià),節(jié)約投資,投用后安全、可靠,降低運(yùn)行費(fèi)用,降低電價(jià)等。具有極其重要的意義。
2.常見的常規(guī)35kv變電站設(shè)計(jì)
35kV高壓配電裝置,采用戶外裝置,斷路器選用DWI2―35戶外多油斷路器,10kV高壓配電裝置采用戶內(nèi)裝置,選用GG―1A(F)高壓開關(guān)柜,配SN10―10少油斷路器或ZN一10戶內(nèi)高壓真空斷路器,繼電保護(hù)屏和控制屏均選用PK型,繼電保護(hù)采用電磁式繼電器。這種設(shè)計(jì)方案最突出的問(wèn)題是設(shè)備落后,結(jié)構(gòu)不夠合理,占地多,投資大,損耗高,效率低,尤其是在一次開關(guān)和二次設(shè)備選型問(wèn)題上,基本停留在5O一60年代的水平,現(xiàn)在正在逐步被新的設(shè)計(jì)方案所代替,但是,由于其運(yùn)行可靠,安裝、運(yùn)行、維護(hù)、檢修技術(shù)力量較容易解決,一般在技術(shù)力量相對(duì)薄弱的偏遠(yuǎn)山區(qū)的縣、鄉(xiāng)鎮(zhèn)35kV變電站仍將長(zhǎng)期采用。
3.按負(fù)荷的重要性和防塵防污特殊要求選擇設(shè)計(jì)方案
此種變電站一般都是專門為大型工礦企業(yè)提供電力的專用變電站。變電站的負(fù)荷均為重要負(fù)荷,因此對(duì)變電站的供電可靠性要求較高,要求戶外裝置都要有一定的防塵防污的性能。
這種設(shè)計(jì)方案也屬于常規(guī)35kV變電站。與前者相比,土地占用相對(duì)減少。但對(duì)設(shè)備要求較高。使得設(shè)備投資費(fèi)用相對(duì)增加。
4.從節(jié)省投資、減輕用戶經(jīng)濟(jì)負(fù)擔(dān)、減少運(yùn)行費(fèi)用的角度考慮設(shè)計(jì)方案
這種變電站一般為35kV簡(jiǎn)易變電站。是一種非常典型的投資少、見效快、建設(shè)周期短的簡(jiǎn)易應(yīng)急變電站。這種設(shè)計(jì)型式的變電站在我地區(qū)近兩年的農(nóng)網(wǎng)改造工程中得到了比較廣泛的應(yīng)用。例如一新建變電站,該站所在的鄉(xiāng)位于山區(qū),此鄉(xiāng)人口稀少,主要經(jīng)濟(jì)收入來(lái)自中藥加工業(yè)和養(yǎng)殖業(yè),用電負(fù)荷不是很大,且基本上都是民用負(fù)荷,同時(shí)該地區(qū)供電最大距離有上百公里,供電電壓不能滿足要求,且線損較大。為了降低損耗必須采用35kV線路送電,考慮以上因素,就決定采取這種簡(jiǎn)易設(shè)計(jì)方案:主變?nèi)萘?150kVA一臺(tái),35kV進(jìn)線一回,主變壓器用高壓熔斷器保護(hù),10kV出線三回,用柱上真空開關(guān)作為線路保護(hù),整個(gè)站采用戶外敞開式布置,無(wú)人值班,這樣只投入了很少的資金就解決了當(dāng)?shù)剞r(nóng)民的用電問(wèn)題。這種方案,適用于經(jīng)濟(jì)比較落后、資金籌集困難的偏遠(yuǎn)、貧困山區(qū)的鄉(xiāng)鎮(zhèn)小容量35kV簡(jiǎn)易小型變電站,我地區(qū)農(nóng)網(wǎng)中有多數(shù)鄉(xiāng)鎮(zhèn)簡(jiǎn)易變電站都采用了這種方式,值得一提的是,此類變電站應(yīng)在設(shè)計(jì)、布置、征地問(wèn)題上為今后的擴(kuò)容計(jì)改留有余地。
5.從技術(shù)進(jìn)步的角度選擇設(shè)計(jì)方案
5.1微機(jī)控制、集成電路保護(hù)35kV小型變電站
此類變電站的高壓設(shè)備與一般變電站的配置情況基本相同,所不同的是在設(shè)備的控制與保護(hù)方面采用了比較先進(jìn)的技術(shù),保護(hù)和控制部分都有微機(jī)來(lái)實(shí)現(xiàn)。微機(jī)通過(guò)數(shù)據(jù)采集系統(tǒng)采集電力系統(tǒng)運(yùn)行的實(shí)時(shí)參數(shù),經(jīng)過(guò)一系列的加工處理通過(guò)顯示屏反饋給運(yùn)行人員,運(yùn)行人員根據(jù)這些信息作出決策后,通過(guò)小鍵盤對(duì)電力系統(tǒng)進(jìn)行控制。當(dāng)系統(tǒng)發(fā)生故障時(shí),CPU根據(jù)采集到的信息,通過(guò)一定的算法,實(shí)現(xiàn)一定的保護(hù)功能,若配備打印機(jī)就可利用微機(jī)的記憶功能。打印出故障種類及短路故障前后的故障參數(shù).便于分析和處理事故,同時(shí)對(duì)微機(jī)保護(hù)裝置來(lái)說(shuō),幾乎不用調(diào)試,這就大大減少了運(yùn)行維護(hù)量,也減少了由于維護(hù)人員維護(hù)不良而造成的事故。此外計(jì)算機(jī)在程序的指揮下,有很強(qiáng)的自診斷能力,不斷檢查、診斷保護(hù)本身故障,并能自動(dòng)識(shí)別和排除干擾,以防止由于干擾而造成的誤動(dòng)作.具有很高的可靠性,再次。各類型微機(jī)保護(hù)所使用的計(jì)算機(jī)硬件和外圍設(shè)備都可通用,不同原理、特性和功能的微機(jī)保護(hù)主要取決于軟件,計(jì)算機(jī)還有自適應(yīng)能力。它可根據(jù)系統(tǒng)接線和運(yùn)行情況的變化而自動(dòng)改變定值。
從而可靈活適應(yīng)電力系統(tǒng)運(yùn)行方式的變化。除了保護(hù)采用微機(jī)實(shí)現(xiàn)外。遠(yuǎn)動(dòng)技術(shù)也實(shí)現(xiàn)了微機(jī)化,采用劈數(shù)變換技術(shù),遙測(cè)精度大為提高,采用了分時(shí)多路復(fù)用技術(shù),遙測(cè)的路數(shù)也增多了,采用了抗干擾編碼技術(shù),使傳輸?shù)目煽啃砸驳玫搅颂岣摺?/p>
近幾年在縣所建的幾個(gè)變電站都采用了這種設(shè)計(jì)形式。設(shè)計(jì)方案為:35kV進(jìn)線一回,10kV出線六回,35kV、10kV均采用戶外裝置,保護(hù)屏選用的是微機(jī)保護(hù)屏,保護(hù)配置為:主變保護(hù)采用微機(jī)差動(dòng)保護(hù)作為主保護(hù),三段式復(fù)壓閉鎖過(guò)電流保護(hù)作為后備保護(hù),還有重瓦斯保護(hù)、輕瓦斯保護(hù)作為本體保護(hù),10kV線路保護(hù)采用二段式相間過(guò)流保護(hù)。且有三相一次重合閘、過(guò)負(fù)荷報(bào)警等功能。上述所有保護(hù)功能都有微機(jī)來(lái)實(shí)現(xiàn)。
這種設(shè)計(jì)方案與通常同容量的35kV變電站相比。減少了占地面積。減少了投資,也便于安裝和運(yùn)行維護(hù),其控制、測(cè)量、保護(hù)、信號(hào)及電源裝置都采用了計(jì)算機(jī)技術(shù),保護(hù)功能完善、通用性強(qiáng)、整定精度高、動(dòng)作離散值小、動(dòng)作速度快,同時(shí)遠(yuǎn)動(dòng)也采用了計(jì)算機(jī)技術(shù),信息傳輸更加可靠和準(zhǔn)確。微機(jī)控制、集成電路保護(hù)35kV小型變電站還可以按全戶內(nèi)式設(shè)計(jì)。
第二篇:許昌110 kV橫山變電站漯河220kV董莊變電站信陽(yáng)110kV濱湖
許昌110 kV橫山變電站、漯河220kV董莊變電站、信陽(yáng)110kV濱湖變電站、周口110kV變電站工程安全檢查通報(bào)
根據(jù)河南省電力公司《關(guān)于開展基建標(biāo)準(zhǔn)化深化應(yīng)用工作的通知》(基〔2010〕46號(hào))及國(guó)家電網(wǎng)公司《輸變電工程施工現(xiàn)場(chǎng)安全通病及防治措施》(2010年版)、《監(jiān)理項(xiàng)目部標(biāo)準(zhǔn)化管理手冊(cè)》要求,公司質(zhì)安部與電網(wǎng)工程二部共同對(duì)許昌110 kV橫山變電站、漯河220kV董莊變電站、信陽(yáng)110kV濱湖變電站、周口110kV變電站工程進(jìn)行了安全標(biāo)準(zhǔn)化檢查,現(xiàn)將檢查結(jié)果通報(bào)如下:
許昌110 kV橫山變電站對(duì)現(xiàn)場(chǎng)進(jìn)行了檢查、漯河220kV董莊變電站、信陽(yáng)110kV濱湖變電站工程對(duì)現(xiàn)場(chǎng)及監(jiān)理項(xiàng)目部資料部分進(jìn)行了檢查、周口110kV變電站工程對(duì)監(jiān)理項(xiàng)目部資料進(jìn)行了檢查(11月上旬對(duì)現(xiàn)場(chǎng)進(jìn)行了安全檢查)。
總體看法,110kV工程的施工現(xiàn)場(chǎng)及監(jiān)理項(xiàng)目部資料較220kV董莊變電站工程現(xiàn)場(chǎng)及資料差。與監(jiān)理項(xiàng)目部標(biāo)準(zhǔn)化工作手冊(cè)要求,差距就更大一些了。本次檢查220kV董莊變電站工程現(xiàn)場(chǎng)安全文明施工情況按照國(guó)網(wǎng)公司的要求做的比較到位。其它工程現(xiàn)場(chǎng)較亂,文明施工較差。
存在的問(wèn)題,主要表現(xiàn)在有的工程監(jiān)理項(xiàng)目部自身應(yīng)編制的安全管理資料不完整、不齊全。如有的項(xiàng)目部未編制監(jiān)理項(xiàng)目部應(yīng)急預(yù)案、危險(xiǎn)源辨識(shí)及預(yù)控措施;編制的安全監(jiān)理工作方案(安全監(jiān)理實(shí)施細(xì)則)、應(yīng)急預(yù)案、安全監(jiān)理管理制度未按國(guó)網(wǎng)公司要求的格式、制度名細(xì)等的要求編寫;安全旁站與國(guó)網(wǎng)公司安全旁站的項(xiàng)目要求差距過(guò)大;安全檢查簽證有些項(xiàng)目什么也都未做、有些做了也不符合國(guó)網(wǎng)公司的要求;方案或作業(yè)指導(dǎo)書編、審、批不規(guī)范;業(yè)主、監(jiān)理、施工項(xiàng)目部安全、質(zhì)量目標(biāo)不一致;數(shù)碼照片分類不規(guī)范、整理不及時(shí)、拍攝質(zhì)量不符合要求等。
一、許昌110 kV橫山變電站工程
1、現(xiàn)場(chǎng)存在問(wèn)題:
1.1 一個(gè)開關(guān)接兩個(gè)用電設(shè)備;接地纏繞及接地連接不牢固;
1.2 孔洞無(wú)蓋板;
1.3 梯子使用不規(guī)范;(梯子的最高兩檔不得站人)
1.4 消防器材不防凍。
二、漯河220kV董莊變電站工程
1、資料存在問(wèn)題
1.1安全強(qiáng)制性條文實(shí)施細(xì)則未編制;(也可與質(zhì)量強(qiáng)制性條文實(shí)施細(xì)則統(tǒng)一編制)
1.2 無(wú)安全檢查簽證記錄。(至少目前應(yīng)有施工用電檢查簽證、工程項(xiàng)目開工兩個(gè)安全檢查簽證)
2、現(xiàn)場(chǎng)存在問(wèn)題
2.1保護(hù)零線重復(fù)接地接地體過(guò)小;(電力安全工作規(guī)程規(guī)定接地體直徑應(yīng)為Ф16mm園鋼,截面積應(yīng)大于190mm)
2三、信陽(yáng)110kV濱湖變電站工程
1、資料存在問(wèn)題 1.1安全監(jiān)理實(shí)施細(xì)則編制人未簽字;應(yīng)急預(yù)案無(wú)編制人、審核人及批準(zhǔn)人簽字;
1.2無(wú)安全旁站工作計(jì)劃;
1.3強(qiáng)制性條文執(zhí)行缺少安全部分施工單位編制的計(jì)劃表及記錄表;
2、現(xiàn)場(chǎng)存在問(wèn)題
2.1接地體過(guò)小;接零不規(guī)范(纏繞);
2.2腳手架無(wú)剪刀撐;斜道欄桿搭設(shè)不規(guī)范;
三、扶溝110kV變電站工程
1、資料存在問(wèn)題 1.1未編制應(yīng)急預(yù)案; 1.2安全旁站記錄不齊全;
1.3強(qiáng)制性條文檢查表填寫不規(guī)范。
二○一○年十二月三十一日
第三篇:kV輸電線路工作總結(jié)
35kV南山——馬蓮溝輸電線路完工總結(jié)
2011年1月
建設(shè)單位:
延長(zhǎng)石油直羅采油廠
設(shè)計(jì)單位:
西安中邦電力咨詢?cè)O(shè)計(jì)有限公司
監(jiān)理單位:
陜西地方電力監(jiān)理公司
施工單位:
延安飛鴻電氣安裝公司
本工程開工時(shí)間:2010年03月
實(shí)際竣工日期:
2010年12月
35kV南山——馬蓮溝輸電線路工程已于2010年12月23日基本完工,在過(guò)去的時(shí)間里,我公司35kV南山——馬蓮溝輸電線路工程實(shí)行了全過(guò)程的項(xiàng)目管理,我部在業(yè)主和建設(shè)單位的正確領(lǐng)導(dǎo)、設(shè)計(jì)的積極指導(dǎo)下,我公司嚴(yán)格按照合同管理的要求,在施工中采取了一系列行之有效的方法,確保了35kV南山——馬蓮溝輸電線路工程的安全和質(zhì)量。
工程簡(jiǎn)介
本線路工程起點(diǎn)為南山35KV變電站的35kV出線構(gòu)架起出線向東北走線,在采油廠東南側(cè)山上左轉(zhuǎn)跨過(guò)后和尚塬村東北側(cè)左轉(zhuǎn)沿去馬蓮溝東側(cè)山上走線,在寨子坪東側(cè)左轉(zhuǎn)下山,沿川道向北走線至樺溝和馬蓮溝交叉處右轉(zhuǎn),后沿馬蓮溝東側(cè)山上走線至馬蓮溝35KV變電站。本線路按單回路設(shè)計(jì)全長(zhǎng)27.3km。線路經(jīng)過(guò)除36#
——70#為平地外,其余地形全部為山地,故其工程地質(zhì)條件較差。線路可利用公路不多,人力運(yùn)輸距離較遠(yuǎn)。本工程共計(jì)桿塔94基,全部為組立鐵塔。線路采用的耐張和轉(zhuǎn)角塔為24基,直線塔為70基。導(dǎo)線采用LGJ-150/25型鋼芯鋁絞線,地線一根采用GJ-35鍍鋅鋼絞線。整條線路除兩端變電站進(jìn)線檔不架設(shè)地線,1#——94#之間全線路架設(shè)單地線。絕緣子型號(hào)為XP—70,耐張塔采用單串5片成串,直線采用單串4片成串。線路金具采用97修訂本產(chǎn)品樣本為準(zhǔn)。導(dǎo)線耐張線夾采用NL-150/25型,懸垂線夾采用CL-150/25型;地線耐張線夾采用NL-35/G,直線采用CL-4/G。本次線路跨越在建高速一處、房屋兩處、10kv線路五處、通訊線路13處。
工程完成情況
35kV南山——馬蓮溝輸電線路工程2010年12月三級(jí)驗(yàn)收自檢完畢。
35kV南山——馬蓮溝輸電線路工程,由于各種原因,工程時(shí)間緊、任務(wù)重、要求高,通過(guò)以往工程經(jīng)驗(yàn)的總結(jié),我們對(duì)工程的重要性有充分的認(rèn)識(shí),所以要保證工程安全優(yōu)質(zhì)、確保工期、提高效益。總體目標(biāo)要把本工程建設(shè)成“達(dá)標(biāo)投產(chǎn)”和“零缺陷工程”。
在本次工程施工過(guò)程中我部,認(rèn)真職守,抓質(zhì)量,抓安全生產(chǎn),要求施工隊(duì)做好各道工序控制關(guān),嚴(yán)格按圖紙施工。對(duì)鐵塔基礎(chǔ)澆制部分進(jìn)行現(xiàn)場(chǎng)旁站,對(duì)澆制需要的沙石、水泥、鋼筋等材料進(jìn)行細(xì)致的檢驗(yàn),對(duì)混凝土的配比作出嚴(yán)格要求。現(xiàn)場(chǎng)澆制是對(duì)基礎(chǔ)的方量,鋼筋的捆綁進(jìn)行全面的檢驗(yàn),確保了基礎(chǔ)的質(zhì)量。堅(jiān)持基礎(chǔ)澆制基面一次性成功,杜絕磨面,采取儀器找準(zhǔn),及時(shí)綜合處理,一步到位的成功工藝。基礎(chǔ)澆制后要求施工隊(duì)加大成品保護(hù)力度,對(duì)已完工基礎(chǔ)進(jìn)行有效的保護(hù)。對(duì)桿塔中塔件,架線中的金具、導(dǎo)、地線等外部質(zhì)量和相應(yīng)試驗(yàn)報(bào)告的檢查,對(duì)于組塔采取現(xiàn)場(chǎng)監(jiān)督,嚴(yán)格遵循圖紙?jiān)O(shè)計(jì),杜絕施工過(guò)程中發(fā)生安全事故,我部要求施工隊(duì)對(duì)塔件按段號(hào)合理擺放,現(xiàn)場(chǎng)螺栓分類標(biāo)識(shí),進(jìn)行清點(diǎn),以防止錯(cuò)裝、混裝,對(duì)自立式鐵塔的吊裝,采用了優(yōu)質(zhì)的合成吊裝帶起吊塔件,防止了塔件鍍鋅的破壞和塔件的變形。尤其是耐張塔型的組立施工中,要求工隊(duì)先驗(yàn)基礎(chǔ)后組塔,先下端校正緊固,后上端安裝.架線施工工序多,工藝難度大我部要求施工隊(duì)對(duì)架線施工按施工說(shuō)明、施工準(zhǔn)備、導(dǎo)地線張力展放、緊掛線、附件安裝、導(dǎo)地線壓接進(jìn)行嚴(yán)格控制。針對(duì)本工程跨越鐵路,辦理跨越手續(xù)難度大對(duì)施工時(shí)間要求緊,工隊(duì)做到具體、有針對(duì)性,確保安全施工萬(wàn)無(wú)一失。
通過(guò)我們的共同努力,本工程各分部工程中間驗(yàn)收工程質(zhì)量合格,工程竣工驗(yàn)收工程質(zhì)量合格,滿足業(yè)主工程“達(dá)標(biāo)投產(chǎn)”、創(chuàng)“優(yōu)質(zhì)工程”的標(biāo)準(zhǔn)要求。
本線路施工中存在的問(wèn)題
1、資料管理工作還需進(jìn)一步標(biāo)準(zhǔn)化、規(guī)范化、做到工程資料及時(shí)收集、及時(shí)整理和及時(shí)歸檔。
2、鐵塔材料短缺嚴(yán)重,導(dǎo)致工程誤工嚴(yán)重。
3、基礎(chǔ)回填沒有夯實(shí),導(dǎo)致降雨后基礎(chǔ)下陷嚴(yán)重。
4、部分鐵塔防盜冒失去防盜作用。
35kV南山——馬蓮溝輸電線路監(jiān)理項(xiàng)目部
工程總監(jiān):馮海軍
現(xiàn)場(chǎng)監(jiān)理:唐
鑫
2011年1月
第四篇:北京城北500 kV變電站GIS系統(tǒng)的交流耐壓試驗(yàn)2006概要
第27卷電力建設(shè)??
北京城北500kV 變電站GIS 系統(tǒng)的交流耐壓試驗(yàn) 劉鐵成,程金梁,劉凱樂
(北京送變電公司,北京市,102401 [摘要]城北500kV 變電站GIS 系統(tǒng)的交流耐壓試驗(yàn),根據(jù)GIS 設(shè)備結(jié)構(gòu)復(fù)雜、間隔數(shù)量眾多、整體電容
量較大等特點(diǎn),合理選擇了耐壓設(shè)備組合方式來(lái)滿足試驗(yàn)容量的要求,并采用了母線連同GCB 單元整體加壓的方法。既圓滿完成了試驗(yàn),又最大程度減少了試品的加壓次數(shù),從而降低了對(duì)試品的絕緣損壞。[關(guān)鍵詞] 500kV 變電站GIS 交流耐壓試驗(yàn) 中圖分類號(hào):TM63文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1000-7229(200611-0008-03 收稿日期:2006-09-20 作者簡(jiǎn)介:劉鐵成(1976-,男,從事高電壓試驗(yàn)工作。1工程概況
北京城北變電站本期建設(shè)2臺(tái)1200MVA 的 主變,500kV 進(jìn)線2回,220kV 出線8回。變電站 500kV 系統(tǒng)為內(nèi)橋接線方式,220kV 系統(tǒng)為雙母
線雙分段接線方式,橋斷路器及分段斷路器均斷開運(yùn)行。
城北變電站的220kV 系統(tǒng)、500kV 系統(tǒng)均使用了平高東芝公司生產(chǎn)的GIS 設(shè)備,按照交接試驗(yàn)要求,需對(duì)全站的GIS 系統(tǒng)進(jìn)行交流耐壓試驗(yàn)。城北變電站的GIS 系統(tǒng)規(guī)模較大,220kV 系統(tǒng)包括18個(gè)電氣間隔,500kV 系統(tǒng)包括3個(gè)電氣間隔,電磁式電壓互感器(PT 內(nèi)置于罐體內(nèi)。本次交流耐壓試驗(yàn)要附帶電壓互感器一起進(jìn)行,這就要求在耐壓過(guò)程中除考慮GIS 的耐壓標(biāo)準(zhǔn)外,還需避免PT 發(fā)生諧振,導(dǎo)致鐵芯飽和,從而損害被試品本體。所以,交流耐壓試驗(yàn)的頻率要控制在一定范圍內(nèi),需要制定一個(gè)科學(xué)、完備、安全的交流耐壓試驗(yàn)方案。
2GIS 系統(tǒng)交流耐壓試驗(yàn)方案的確立 2.1GIS 系統(tǒng)交流耐壓試驗(yàn)標(biāo)準(zhǔn)
按照《電氣裝置安裝工程電氣設(shè)備交接試驗(yàn)標(biāo)
準(zhǔn)》(GB50150—91、《氣體絕緣金屬封閉開關(guān)設(shè)備現(xiàn)場(chǎng)交接試驗(yàn)規(guī)程》(DL/T 618—1997、《華北電網(wǎng)有限公司電力設(shè)備交接和預(yù)防性試驗(yàn)規(guī)程》的要求,編制試驗(yàn)方案。GIS 常規(guī)試驗(yàn)項(xiàng)目包括主回路電阻測(cè)量、GIS 元件調(diào)試、SF 6氣體微水含量和檢漏試驗(yàn)等。交流耐壓試驗(yàn)應(yīng)在被試設(shè)備的常規(guī)試驗(yàn)全部結(jié)束,且試驗(yàn)合格后進(jìn)行。
2.2GIS 系統(tǒng)交流耐壓試驗(yàn)流程
GIS 現(xiàn)場(chǎng)交流耐壓試驗(yàn)的第1階段是老練凈化,其目的是清除GIS 內(nèi)部可能存在的導(dǎo)電微粒或
非導(dǎo)電微粒。老練凈化可使導(dǎo)電微粒移動(dòng)到低電場(chǎng)區(qū)或微粒陷阱中,并燒蝕電極表面的毛刺,使其對(duì)絕緣沒有危害作用。老練凈化電壓值應(yīng)低于耐壓試驗(yàn)電壓值,時(shí)間可取15min。第2階段是耐壓試驗(yàn),即在老練凈化過(guò)程結(jié)束后進(jìn)行耐壓試驗(yàn),時(shí)間為1min。
AC Voltage-withstand Test of GIS System at North Beijing 500kV Substation LIU Tie-cheng,CHENG Jin-liang,LIU Kai-le
(Beijing Transmission and Distribution Company,Beijing City,102401 [Abstract ] The AC voltage-w ithstand test of GIS system at north Beijing 500kV substation is characterized by complex structures of GIS equipment, many number of compartment and big capacity of integral capacitance.So it is necessary to select rationally the combination of the voltage-withstanding devices to meet the requirements for the test.A compression method applied on the bus with the integral GCB unit was adopted,which has completed the test and reduced the compression numbers on the samples to the maximum extent.As a result,the insulation damage on the samples was reduced.[Keywords ] 500kV substation;GIS;AC voltage-withstand test 電力建設(shè)
Electric Power Construction 第27卷第11期2006年11月 Vol.27No.11 Nov,2006 8 第11期??
B 1—— —
調(diào)壓器;B 2———激勵(lì)變壓器;U R ———有功損耗的等效電阻;C
1、C 2——— 電容分壓器高、低壓臂電容;C X ———被試品;V ———
電壓表;F ———熔絲;U L ———電抗器。交流耐壓試驗(yàn)的流程:試驗(yàn)準(zhǔn)備→空升試驗(yàn)→耐壓前絕緣電阻測(cè)試→交流耐壓試驗(yàn)→耐壓后絕緣電阻測(cè)試→后期工作。
2.3GIS 系統(tǒng)交流耐壓試驗(yàn)設(shè)備
采用CHX(U-f-4000kVA/800kV 型調(diào)頻式串聯(lián)諧振耐壓試驗(yàn)裝置,其輸出電壓最高可達(dá)到800kV ,輸出電流5A。該設(shè)備的基本原理如圖1所示,在RLC 串聯(lián)回路中,當(dāng)感抗與試品容抗相等時(shí),電抗
中的磁場(chǎng)能量與試品電容中的電場(chǎng)能量相補(bǔ)償,試品所需的無(wú)功功率全部由電抗器供給,電源只供給回路的有功損耗。此時(shí),電路的cos φ=1,即電源電壓與諧振回路電流同相位,電感上的電壓與電容上的壓降大小相等,相位相反,即ωL= ωC
。當(dāng)回路中L、C 參數(shù)固定時(shí),調(diào)節(jié)電源的頻率等于回路諧振頻 率時(shí),即f=1 2πLC ",可產(chǎn)生諧振,此時(shí): Uc=I 1ωC =I ωL
則品質(zhì)因數(shù):Q= Uc U 1=I ωL IR =ωL R 設(shè)備主要技術(shù)參數(shù):電源輸入380V ±10%三相,50Hz;額定試驗(yàn)容量4000kVA;諧振電壓0~ 800kV;頻率調(diào)節(jié)范圍30~300Hz;頻率調(diào)節(jié)分辨率
0.01Hz;波形畸變率不大于1%;電抗器Q 值≥70;電抗器電感量100H/節(jié),共4節(jié);分壓器4節(jié)串聯(lián)分壓比為2000/1。
2.4GIS 系統(tǒng)交流耐壓試驗(yàn)方案2.4.1 交流耐壓試驗(yàn)加壓過(guò)程
試驗(yàn)程序由現(xiàn)場(chǎng)試驗(yàn)人員編制,經(jīng)制造廠和用戶同意后,確定采用圖2的加壓方案。
2.4.2交流耐壓試驗(yàn)方案的設(shè)計(jì)
交流耐壓試驗(yàn)電壓值U t 按《華北電網(wǎng)有限公司
電力設(shè)備交接和預(yù)防性試驗(yàn)規(guī)程》的要求,最終確定為:220kV 系統(tǒng)耐壓值為356kV ,500kV 系統(tǒng)耐
壓值為612kV。試驗(yàn)采用調(diào)頻法,在50%的試驗(yàn)電壓以下進(jìn)行諧振點(diǎn)調(diào)節(jié),GIS 組合電器頻率應(yīng)控制在30~300Hz。考慮到PT 耐壓試驗(yàn)時(shí)對(duì)頻率的要求比較特殊,根據(jù)城北變電站使用PT 的特點(diǎn),將耐壓頻率確定在以下范圍:220kV 系統(tǒng)為120~300Hz , 500kV 系統(tǒng)為60~300Hz。
在交流耐壓試驗(yàn)過(guò)程中,試驗(yàn)電壓應(yīng)施加到每相導(dǎo)體和外殼之間,可以每次一相加壓,一相加壓時(shí)其他相的導(dǎo)體應(yīng)與接地的外殼相連。試驗(yàn)電源可接到被試相導(dǎo)體任一部位。試驗(yàn)程序的設(shè)計(jì)原則上應(yīng)使每個(gè)部件都至少施加1次試驗(yàn)電壓,同時(shí)必須盡可能減少固體絕緣的重復(fù)試驗(yàn)次數(shù)。
2.4.3 220kV GIS 系統(tǒng)交流耐壓試驗(yàn)方案的確定 現(xiàn)場(chǎng)實(shí)測(cè)220kV GIS 系統(tǒng)相關(guān)數(shù)據(jù)如下: 電容量:GCB 單元700pF/相,母線40pF/m ,母線PT 250pF/只,線路PT 200pF/只。
PT 分布:A 相———
母線PT 2只、線路PT 4只;B 相———母線PT 2只;C 相———母線PT 2只。城北變電站220kV GIS 系統(tǒng)共有14個(gè)GCB 單元,若按照常規(guī)試驗(yàn)方法,對(duì)GCB 單元逐個(gè)進(jìn)行耐
壓試驗(yàn),不但耗時(shí)耗力,而且要對(duì)母線多次加壓。交流耐壓試驗(yàn)屬于破壞性試驗(yàn),對(duì)試品反復(fù)加壓會(huì)對(duì)其絕緣造成損傷,所以耐壓方案必須盡可能減少加壓次數(shù)。
根據(jù)現(xiàn)有設(shè)備的容量,我們采取如下加壓方式(以A 相為例,B、C 相參照A 相方法進(jìn)行:(1以GIS 設(shè)備一端的1號(hào)主變進(jìn)線為加壓端,將4號(hào)母線上的所有主刀合閘、地刀分閘,5號(hào)母線上的所有主刀分閘、地刀合閘;靠近1號(hào)主變進(jìn)線的
7個(gè)GCB 單元斷路器合閘;B、C 相從其他出線側(cè)接地。這樣4號(hào)母線、1號(hào)主變進(jìn)線及7個(gè)GCB 單元
能夠耐受電壓。
(2以GIS 設(shè)備另一端的2號(hào)主變進(jìn)線為加壓端,將5號(hào)母線上的所有主刀合閘、地刀分閘,4號(hào)母線上的所有主刀分閘、地刀合閘;靠近2號(hào)主變進(jìn)線的7個(gè)GCB 單元斷路器合閘;B、C 相從其他出線側(cè)接地。這樣5號(hào)母線、2號(hào)主變進(jìn)線及7個(gè)GCB 單元能夠耐受電壓。
圖1串聯(lián)諧振交流耐壓原理圖 圖2交流耐壓試驗(yàn)加壓過(guò)程
北京城北500kV 變電站GIS 系統(tǒng)的交流耐壓試驗(yàn) 9 第27卷 電力建設(shè)??
線用量(使變電站的總長(zhǎng)度和管母線長(zhǎng)度都縮小了 12m ,經(jīng)濟(jì)性較高。間隔寬度變?yōu)?2m 后,我們進(jìn)
行了電氣距離的校驗(yàn)。
出線相間距滿足手冊(cè)中間隔寬度為12m 時(shí)的最小相間距(3750mm 和相對(duì)地距離(2250mm ,懸垂串相間距為3m ,滿足設(shè)備最小相間距,可見增加出線懸垂串后,邊相的對(duì)地距離滿足要求,同時(shí)也減小了導(dǎo)線的風(fēng)擺。
2.3.3主變的布置
主變壓器2組1200MVA 主變壓器布置。采用
單相變壓器,每相容量400MVA ,變壓器單列排列,變壓器間設(shè)置防火墻,主變出口處采用管母線,減小了縱向尺寸。(我們考慮過(guò)本站采用單臺(tái)三相變壓器的型式,因?yàn)椴捎萌嘧儔浩鞯囊淮筇攸c(diǎn)是節(jié)約占地。但是就本站而言,其橫向距離主要由220kV GIS 設(shè)備控制,所以三相變壓器減少占地,節(jié)約投資的特點(diǎn)在本站不明顯。
2.3.4電氣總平面布置的確定
電氣總平面的布置是在各級(jí)電壓配電裝置布置
優(yōu)化的基礎(chǔ)上進(jìn)行組合。結(jié)合總圖專業(yè)的要求,使之在電氣布置上合理,進(jìn)出線順暢、功能分區(qū)明確,所區(qū)總平面規(guī)整,工程總投資經(jīng)濟(jì)。本變電站的電氣總平面布置如圖2所示。
3小結(jié)
該變電站地處北京市近郊,土地資源珍貴,而 GIS 設(shè)備在供電可靠性和節(jié)約土地方面優(yōu)勢(shì)明顯, 故500,200kV 均采用GIS 設(shè)備,節(jié)省占地2.44hm 2。220kV 配電裝置每個(gè)間隔按照12m 設(shè)置,比原來(lái)敞開式布置縮小1m ,既能在電氣距離上滿足要求,又節(jié)省了占地和GIS 設(shè)備的封閉管母線用量,經(jīng)濟(jì)性較
高。該變電站主變低壓側(cè)選擇66kV 電壓等級(jí),既保證今后擴(kuò)建方便及配電裝置的可靠性,又節(jié)省了投資。
(責(zé)任編輯:馬 明 表1 220kV GIS 系統(tǒng)交流耐壓試驗(yàn)結(jié)果
注:使用激勵(lì)變輸出電壓10kV 抽頭,電抗器兩串兩并,加裝均壓環(huán),試驗(yàn)電壓356kV。
表2500kV GIS 系統(tǒng)交流耐壓試驗(yàn)結(jié)果
選擇上述加壓方法可以分相6次完成整個(gè)系統(tǒng)的耐壓工作,而且實(shí)現(xiàn)了所有試驗(yàn)部分僅承受1次加壓,最大程度地減少了對(duì)其絕緣的損傷。
2.4.4500kV GIS 系統(tǒng)交流耐壓方案的確定
現(xiàn)場(chǎng)實(shí)測(cè)500kV GIS 系統(tǒng)相關(guān)數(shù)據(jù)如下:電容量:GCB 單元330pF/相,母線50pF/m ,母
線PT 700pF/只,線路PT 700pF/只。PT 分布:A 相———
母線PT 2只、線路PT 2只;B 相———母線PT 2只;C 相———母線PT 2只。GCB 單元共3個(gè)。
根據(jù)現(xiàn)有設(shè)備的容量,我們采取如下加壓方式:
從任一套管處加壓,每次耐壓一相。所有GCB 單元和主隔離刀處于合閘狀態(tài),所有地刀處于分閘狀態(tài),分3次進(jìn)行。按這樣的方案能夠順利完成交流耐壓試驗(yàn)。
3GIS 系統(tǒng)交流耐壓試驗(yàn)的實(shí)施和結(jié)果
方案制定完成后進(jìn)入最后實(shí)施階段。在試驗(yàn)前,我們考慮到現(xiàn)場(chǎng)試驗(yàn)電暈損耗較大的問(wèn)題,有針對(duì)性地對(duì)耐壓設(shè)備進(jìn)行了改進(jìn),包括:修繕了部分變形的均壓環(huán),選用了直徑300mm 的高壓引線來(lái)代替原有引線,完善操作臺(tái)保護(hù)系統(tǒng)等,為試驗(yàn)順利進(jìn)行
做了充分的準(zhǔn)備工作。試驗(yàn)于2006年5月26、27日進(jìn)行,試驗(yàn)結(jié)果見表1、2。
這次交流耐壓試驗(yàn)均一次通過(guò),升壓過(guò)程中沒有發(fā)生放電和閃絡(luò)現(xiàn)象,且試驗(yàn)數(shù)據(jù)在被試品允許范圍內(nèi),所以GIS 系統(tǒng)交流耐壓順利通過(guò)。
(責(zé)任編輯:李漢才
相別頻率/Hz 調(diào)壓器輸出電壓/V 調(diào)壓器輸出電流/A 輸入電流/A A 122.5928011020 B 137.0326010515C 137.25 265 109 17 相別頻率/Hz 調(diào)壓器輸出電壓/V 調(diào)壓器輸出電流/A 輸入電流/A A 84.0828013835
B 93.1226512028C 91.56 270 126 30 注:使用激勵(lì)變輸出電壓20kV 抽頭,電抗器四串,加裝均壓環(huán),試驗(yàn)電壓612kV。!!!!!!!!!!!!!!!!!!!!!!!(上接第7頁(yè) 10
第五篇:變電站直流系統(tǒng)設(shè)計(jì)方案的合理選擇
變電站直流系統(tǒng)設(shè)計(jì)方案的合理選擇
2009-05-06 14:44:08 來(lái)源: 網(wǎng)上搜集 作者:佚名
摘 要:對(duì)變電站直流系統(tǒng)設(shè)計(jì)中的幾個(gè)主要問(wèn)題進(jìn)行了討論,闡述了影響直流系統(tǒng)額定電壓和蓄電池容量選擇的主要因素,分析了直流系統(tǒng)額定電壓、蓄電池容量的選取方法以及主接線、直流饋線網(wǎng)絡(luò)的設(shè)計(jì)方法,介紹了新型的充電裝置、絕緣監(jiān)測(cè)和電壓監(jiān)視裝置的性能。關(guān)鍵詞:變電站;直流系統(tǒng);設(shè)計(jì);智能型高頻開關(guān)充電裝置;絕緣監(jiān)測(cè)和電壓監(jiān)視裝置
直流系統(tǒng)為變電站的繼電保護(hù)、控制系統(tǒng)、信號(hào)系統(tǒng)、自動(dòng)裝置、UPS和事故照明等提供電源。近年來(lái)直流系統(tǒng)的技術(shù)和設(shè)備發(fā)展迅速,閥控鉛酸蓄電池、智能型高頻開關(guān)充電裝置、微機(jī)型絕緣監(jiān)測(cè)裝置等,具有安全可靠、技術(shù)先進(jìn)和性能優(yōu)越等特點(diǎn),促進(jìn)了直流系統(tǒng)的發(fā)展。
本文就變電站設(shè)計(jì)中對(duì)直流系統(tǒng)設(shè)計(jì)有直接影響的因素和變電站直流系統(tǒng)設(shè)計(jì)方案的選擇進(jìn)行探討。 1直流系統(tǒng)接線
根據(jù)《火力發(fā)電廠和變電所直流系統(tǒng)設(shè)計(jì)技術(shù)規(guī)定》,發(fā)電廠和變電站的直流系統(tǒng)應(yīng)采用單母線或單母線分段接線。單母線接線簡(jiǎn)單、清晰,但可靠性與靈活性差,一般用在110kV以下的變電站;單母線分段接線可靠性較高,任一段母線出現(xiàn)故障或需要檢修都不影響供電,建議110 kV,220 kV和500 kV變電站采用單母線分段接線。 2直流系統(tǒng)額定電壓
在確定變電站直流系統(tǒng)額定電壓時(shí),應(yīng)根據(jù)變電站的具體情況,找出影響直流系統(tǒng)額定電壓選擇的主要因素。以往設(shè)計(jì)的220 kV及以下電壓等級(jí)的變電站,大多數(shù)為帶電磁操作機(jī)構(gòu)的斷路器,需要直流動(dòng)力合閘電源,在這種情況下,滿足直流動(dòng)力回路電壓的要求,降低直流動(dòng)力電纜的投資,成為影響直流系統(tǒng)額定電壓選擇的主要因素,因此,以往設(shè)計(jì)的變電站中多數(shù)采用了220 V的直流系統(tǒng)。20世紀(jì)80年代以來(lái),在220~500 kV變電站中,110 kV及以上電壓等級(jí)的斷路器多采用氣動(dòng)或液壓操作機(jī)構(gòu),10 kV斷路器采用彈簧操作機(jī)構(gòu),這樣就不需要直流系統(tǒng)提供動(dòng)力合閘電源了,因此,滿足直流動(dòng)力回路電壓的要求和降低直流動(dòng)力電纜投資,就不再是確定直流系統(tǒng)額定電壓的主要因素。由于500 kV變電站被控對(duì)象遠(yuǎn),控制回路電纜長(zhǎng),所以滿足控制回路電壓的要求,降低控制電纜的投資就成為確定500 kV變電站直流系統(tǒng)額定電壓的主要因素。一般來(lái)說(shuō),當(dāng)直流電壓為220 V時(shí),若控制電纜長(zhǎng)度在500 m以內(nèi),電纜截面面積不大于4 mm2,就不會(huì)給電纜的接線帶來(lái)困難。當(dāng)直流電壓為110 V時(shí),若電纜長(zhǎng)度超過(guò)250 m,就要選用截面面積為6 mm2或10 mm2的電纜,一般端子排只能連接截面面積不超過(guò)6 mm2的電纜芯,要連接截面面積大的電纜芯必須采取特殊的連接方式,這給施工和維護(hù)都帶來(lái)困難;另外,500 kV變電站的控制對(duì)象多,距離遠(yuǎn),電纜用量大,直流電壓采用110 V,加大了控制電纜的截面面積,必然大幅度增加有色金屬的消耗,增加了在控制電纜方面的投資。基于上述技術(shù)和經(jīng)濟(jì)上的考慮,在220~500 kV變電站采用集中控制的情況下,直流系統(tǒng)的額定電壓宜選220 V。
若220 kV變電站的規(guī)模較小,控制電纜的單根長(zhǎng)度較短和控制電纜總量較少,或?yàn)槿珣魞?nèi)的220 kV變電站的情況下,直流系統(tǒng)的額定電壓采用110 V是合理的。
若500 kV變電站采用在配電裝置上設(shè)分控室,二次設(shè)備分散布置,在主控室和分控室中都設(shè)有獨(dú)立的直流系統(tǒng),則控制電纜的長(zhǎng)度可大大縮短,滿足控制回路電纜電壓的要求不存在任何問(wèn)題。此時(shí),由于變電站的蓄電池組數(shù)多,所以降低每組蓄電池及其輔助設(shè)施的造價(jià)就顯得尤為突出。在這種情況下變電站的直流系統(tǒng)的額定電壓宜選110 V。3直流饋線網(wǎng)絡(luò)
為簡(jiǎn)化設(shè)備,220 kV變電站直流系統(tǒng)一般采用環(huán)形供電網(wǎng)絡(luò),即直流動(dòng)力負(fù)荷和控制負(fù)荷都采用環(huán)形供電網(wǎng)絡(luò)。在變電站內(nèi)設(shè)動(dòng)力和控制小母線,在各直流負(fù)荷之間形成環(huán)形供電網(wǎng)絡(luò),每個(gè)環(huán)的電源回路接到兩段母線上。若220 kV變電站為全戶內(nèi)式,220 kV及110 kV配電裝置均采用氣體絕緣金屬封閉開關(guān)設(shè)備(GIS),二次設(shè)備置于GIS室內(nèi),則直流饋線應(yīng)分別引至各配電裝置處各自形成環(huán)網(wǎng)。由于GIS二次回路所需直流電源較多,故在設(shè)計(jì)時(shí)應(yīng)考慮足夠的直流饋線數(shù)量。
500 kV變電站對(duì)直流供電網(wǎng)的可靠性要求更高,結(jié)合對(duì)控制電源雙重化的要求,一般采用輻射狀供電。為了簡(jiǎn)化供電網(wǎng)絡(luò),減少饋線電纜數(shù)量,可在靠近配電裝置處設(shè)直流分屏,每一分屏由2組蓄電池各用1條饋線供電。 4蓄電池容量
在以往的變電站中,10 kV斷路器多采用電磁操作機(jī)構(gòu),其額定合閘電流較大,為90~245 A,所以事故放電末期承受沖擊負(fù)荷時(shí),確保直流母線電壓在允許值范圍內(nèi),是選擇蓄電池容量的決定性因素。近年來(lái),越來(lái)越多的10 kV斷路器采用彈簧操作機(jī)構(gòu),其合閘電流很小,則蓄電池的容量由全站的經(jīng)常負(fù)荷和事故負(fù)荷決定,這樣可大大減少蓄電池容量。
以1個(gè)具有2臺(tái)150~180 MVA主變壓器、8回220 kV線路、10回110 kV線路、10回10 kV線路和2組電容器的220 kV變電站為例,當(dāng)變電站10 kV斷路器采用彈簧操作機(jī)構(gòu)時(shí),其額定合閘電流為3.2 A,分閘電流為0.5 A,允許的最低工作電壓為87.5%額定電壓,選擇220 V額定電壓、104只蓄電池和400 Ah容量的直流系統(tǒng)即可滿足要求。 5充電裝置
充電裝置是保證蓄電池可靠運(yùn)行的主要設(shè)備,特別是閥控式蓄電池對(duì)充電裝置性能的要求更高。以往的變電站的充電裝置多采用晶閘管整流裝置,近年來(lái)越來(lái)越多的變電站采用智能型高頻開關(guān)充電裝置,且運(yùn)行情況良好。智能型高頻開關(guān)充電裝置具有技術(shù)先進(jìn)、性能優(yōu)越和體積小等優(yōu)點(diǎn)。表1列出了2種類型的充電裝置的技術(shù)指標(biāo)。 6絕緣監(jiān)測(cè)和電壓監(jiān)視裝置
常用的直流絕緣監(jiān)測(cè)和電壓監(jiān)視裝置是根據(jù)電橋原理由繼電器組成的,近年來(lái)有些廠家生產(chǎn)了微機(jī)型的直流絕緣監(jiān)測(cè)和電壓監(jiān)視裝置,如南京自動(dòng)化研究院的ZYJ型絕緣監(jiān)測(cè)和電壓監(jiān)視裝置,武漢琴臺(tái)電力技術(shù)研究院的WZJ型絕緣監(jiān)測(cè)和電壓監(jiān)視裝置,溫州星炬電控有限公司的ZJD-4型絕緣監(jiān)測(cè)和電壓監(jiān)視裝置等。這些產(chǎn)品的靈敏度高,正、負(fù)母線絕緣同時(shí)降低時(shí)也能進(jìn)行監(jiān)測(cè),并帶有分支回路在線監(jiān)測(cè)裝置,能指出絕緣下降或出現(xiàn)接地故障的回路,大大縮短了查找直流系統(tǒng)接地故障的時(shí)間。
采用單母線分段接線方式有2組蓄電池時(shí),母線是分開運(yùn)行的,以往多設(shè)1套直流絕緣監(jiān)測(cè)和電壓監(jiān)視裝置,經(jīng)切換開關(guān)切換至2段母線,接線復(fù)雜,其中有一段母線不能監(jiān)測(cè),所以每組母線設(shè)1套直流絕緣監(jiān)測(cè)和電壓監(jiān)視裝置為好;只有1組蓄電池但采用單母線分段接線方式時(shí),單分段開關(guān)通常是接通的,此時(shí)可設(shè)1套可切換的直流絕緣監(jiān)測(cè)和電壓監(jiān)視裝置。 7結(jié)束語(yǔ)
直流系統(tǒng)是變電站的一個(gè)重要組成部分,對(duì)變電站的正常運(yùn)行起著重要的作用,它的設(shè)計(jì)方案的合理性及其運(yùn)行的可靠性直接影響著變電站的可靠性。所以在變電站直流系統(tǒng)的設(shè)計(jì)中,我們要根據(jù)變電站的實(shí)際情況對(duì)直流系統(tǒng)進(jìn)行計(jì)算、分析,選擇最合理的方案。 參考文獻(xiàn)